Schneider Acti9 iDPN Vigi RCBO in Malaysia: voltage-independent, 10mA options and the 16A limit

The Acti9 iDPN Vigi is Schneider’s 1P+N RCBO: one device that protects a circuit against overload, short circuit and earth leakage. It matters for Malaysian homes for two reasons. Schneider Malaysia’s pages for the models below rate it to EN/IEC 61009-2-1, the standard for voltage-independent RCBOs, which some electricians insist on. And the Malaysian list includes 10mA models, the sensitivity the Energy Commission requires on water-heater circuits. The catch is that the 10mA versions stop at 16A.

Schneider Acti9 iDPN Vigi RCBOs

Schneider's Acti9 iDPN Vigi 1P+N RCBOs on Schneider Malaysia's product list (55 references, rated to EN/IEC 61009-2-1, including three 10 mA Type A models (10 A and 16 A). Rows shown are a selected set.

Family
Acti9 iDPN Vigi
Function
RCBO — overload, short-circuit and earth-leakage protection
Poles
1P+N, one protected pole (some pages say "2P with 1 protected pole")
Sub-ranges
iDPN N 42 refs (6 kA), iDPN H 11 (10 kA), iDPNa 2 (4.5 kA)
Sensitivity on the Malaysian list
10 mA (Type A: A9D02610 10 A C, A9D02616 16 A C, A9D08616 16 A B), 30 mA, 100 mA, 300 mA; a separate se.com/my page exists for A9D08610 (10 A B, 10 mA) outside the range list
Standard
EN/IEC 61009-2-1 in the 7 resolved Malaysian descriptions (10/30 mA refs across N, H and iDPNa)
Width
36 mm (4 × 9 mm) in the 7 resolved descriptions
Rows shown
24 selected references (all 10 mA; iDPN N 30 mA Type A and AC C-curve; iDPN H 30 mA Type A C-curve); the full Malaysian list is summarised in the article
Selected variants
ModelConfiguration
A9D02610Acti9 iDPN N Vigi RCBO, 1P+N, 10 A, C curve, 6000 A, 10 mA, Type A
A9D02616Acti9 iDPN N Vigi RCBO, 1P+N, 16 A, C curve, 6000 A, 10 mA, Type A
A9D08616Acti9 iDPN N Vigi RCBO, 1P+N, 16 A, B curve, 6000 A, 10 mA, Type A
A9D37606Acti9 iDPN H Vigi RCBO, 1P+N, 6 A, C curve, 10000 A, 30 mA, Type A
A9D37610Acti9 iDPN H Vigi RCBO, 1P+N, 10 A, C curve, 10000 A, 30 mA, Type A
A9D37616Acti9 iDPN H Vigi RCBO, 1P+N, 16 A, C curve, 10000 A, 30 mA, Type A
A9D37620Acti9 iDPN H Vigi RCBO, 1P+N, 20 A, C curve, 10000 A, 30 mA, Type A
A9D37625Acti9 iDPN H Vigi RCBO, 1P+N, 25 A, C curve, 10000 A, 30 mA, Type A
A9D37632Acti9 iDPN H Vigi RCBO, 1P+N, 32 A, C curve, 10000 A, 30 mA, Type A
A9D32606Acti9 iDPN N Vigi RCBO, 1P+N, 6 A, C curve, 6000 A, 30 mA, Type A
A9D32610Acti9 iDPN N Vigi RCBO, 1P+N, 10 A, C curve, 6000 A, 30 mA, Type A
A9D32613Acti9 iDPN N Vigi RCBO, 1P+N, 13 A, C curve, 6000 A, 30 mA, Type A
A9D32616Acti9 iDPN N Vigi RCBO, 1P+N, 16 A, C curve, 6000 A, 30 mA, Type A
A9D32620Acti9 iDPN N Vigi RCBO, 1P+N, 20 A, C curve, 6000 A, 30 mA, Type A
A9D32625Acti9 iDPN N Vigi RCBO, 1P+N, 25 A, C curve, 6000 A, 30 mA, Type A
A9D32632Acti9 iDPN N Vigi RCBO, 1P+N, 32 A, C curve, 6000 A, 30 mA, Type A
A9D32640Acti9 iDPN N Vigi RCBO, 1P+N, 40 A, C curve, 6000 A, 30 mA, Type A
A9D31606Acti9 iDPN N Vigi RCBO, 1P+N, 6 A, C curve, 6000 A, 30 mA, Type AC
A9D31610Acti9 iDPN N Vigi RCBO, 1P+N, 10 A, C curve, 6000 A, 30 mA, Type AC
A9D31616Acti9 iDPN N Vigi RCBO, 1P+N, 16 A, C curve, 6000 A, 30 mA, Type AC
A9D31620Acti9 iDPN N Vigi RCBO, 1P+N, 20 A, C curve, 6000 A, 30 mA, Type AC
A9D31625Acti9 iDPN N Vigi RCBO, 1P+N, 25 A, C curve, 6000 A, 30 mA, Type AC
A9D31632Acti9 iDPN N Vigi RCBO, 1P+N, 32 A, C curve, 6000 A, 30 mA, Type AC
A9D31640Acti9 iDPN N Vigi RCBO, 1P+N, 40 A, C curve, 6000 A, 30 mA, Type AC
Sources

What Schneider Malaysia lists

As of 6 October 2026, Schneider Malaysia’s iDPN Vigi list has 55 references in three sub-ranges:

Sub-rangeReferencesBreaking capacitySensitivitiesTypesRatings
iDPN N Vigi426000A10, 30, 100, 300mAA, AC6–40A (incl. 13A), B and C curve
iDPN H Vigi1110000A30, 300mAA, A-SI6–32A, C curve (one B: A9D07620)
iDPNa Vigi24500A30mAA, AC16A B curve only

Type AC detects ordinary AC leakage. Type A also detects pulsating DC leakage from electronics. A-SI is on two iDPN H models (A9D38610 at 30mA, A9D48616 at 300mA). Not every combination exists. For example, 30mA Type A in iDPN N runs from 6 to 40A with C curve, but 100mA only comes at 10, 16 and 20A.

The Malaysian product pages we checked (seven, across all three sub-ranges) describe these features:

  • one protected pole, worded as “1P+N” on some pages and “2P with 1 protected pole” on others;
  • 36mm wide (four 9mm modules), twice the width of an Easy9 RCBO;
  • an earth fault indicator on the front face that, in Schneider’s words, “allows quick identification of the type of default”.

If it works as Schneider describes, it may address a common objection from Malaysian electricians: that when an RCBO trips, you can’t tell whether it was overload or leakage. Check it on the device.

The 10mA models and water heaters

Three iDPN Vigi references on the Malaysian list are 10mA, all iDPN N, Type A and 6kA:

  • A9D02610: 10A, C curve
  • A9D02616: 16A, C curve
  • A9D08616: 16A, B curve

The Energy Commission’s water-heater guideline (GP/ST/No.6/2016, Table 6) sets minimum ratings for the circuit’s MCB/RCD:

  • 16A for heaters under 2,856W;
  • 20A up to 3,570W;
  • 25A up to 4,462W;
  • 32A up to 5,711W.

So a 16A iDPN 10mA RCBO suits only a heater under about 2.86kW, and a 10A model is below the guideline’s 16A minimum for any water heater. For bigger heaters, Schneider Malaysia’s lists offer three 10mA routes:

  • the Easy9 RCBO at 25 or 32A. It’s 1P+N, so the same 2-pole check below applies, and its datasheet cites the voltage-dependent standard. Of these, only its 32A model, EZ9D16632, covers the 32A band;
  • a 2-pole 25A 10mA RCCB with an MCB, which covers heaters up to about 4.46kW. The Easy9 RCCB offers this, and so does the Acti9 iID range (A9R10225 Type AC, A9R20225 Type A, A9R30225 Type A-SI);
  • the Vigi iC60 block A9V10225 on a 2-pole iC60 MCB: 2-pole, 25A, Type AC, and the one combination whose Schneider pages state voltage independence and 10mA together, at several times the price.

The same guideline asks for a 2-pole RCD on a single-phase heater circuit. The iDPN Vigi has one protected pole, so confirm with the supplier how it switches the neutral if your installer needs to meet that. Our water heater guide covers ratings, cable and the 2-pole question.

Compared with Schneider’s other RCBOs in Malaysia

Easy9 RCBOActi9 iDPN VigiActi9 iC60 RCBO
Poles1P+N1P+N (1 protected)2P (both protected), one 3P
10mA on the Malaysian list25A, 32A10A, 16Anone
Standard citedIEC 61009-2-2, voltage-dependent (datasheet)EN/IEC 61009-2-1, voltage-independent (pages checked)EN/IEC 61009-2-1
Width18mm36mm (pages checked)36mm (2P)

See the Easy9 RCBO and iC60 RCBO pages for details.

Where to find them

  • KVC, a Malaysian electrical distributor, lists A9D42610 (10A, 300mA, Type A), with prices for signed-in accounts.
  • Lazada and Shopee have store listings for A9D31616 (30mA Type AC, 16A C), including this Lazada listing.

A Shopee listing offers a “Schneider 10mA … IDPN” leakage switch, and cross-border import sites list an “iDPNa 10mA”. On Schneider Malaysia’s list, iDPNa only comes in 30mA. The only 10mA models on its iDPN Vigi list are the three above, though a separate Schneider Malaysia page also exists for A9D08610 (10A B curve). Ask the seller for the exact reference and check it against Schneider Malaysia’s page and the ST-SIRIM label before buying. Import-site listings aren’t local stock.