RCCBs in Malaysia: sensitivity, Type A versus Type AC, and what to order
An RCCB — residual current circuit breaker — is the device that watches for current leaking to earth. It compares the current flowing out on the live conductor with the current coming back on the neutral. When the two differ by more than its sensitivity setting, some current is finding another path — through a faulty appliance, a damaged cable, or a person — and the RCCB disconnects.
That’s a different job from an MCB, which only protects wiring against overload and short circuit. An RCCB has no thermal-magnetic overcurrent protection of its own, so it needs coordinated overcurrent protection elsewhere in the circuit — an upstream or paired MCB — to clear an overload or short circuit. A single device that does both is an RCBO: overcurrent and residual protection combined in one unit. If your board has separate MCBs with one RCCB on the incoming side, you have the split arrangement; an RCBO puts both functions in a single device. An RCCB doesn’t protect against voltage surges either; that’s a surge protective device, which the Energy Commission’s example layouts place after the main switch and ahead of the RCCBs.
Four specifications, not one
Something like “2P 40A 30mA Type A” is four independent properties, and getting any one wrong gives you the wrong device.
Poles. Two-pole (2P) devices suit single-phase supplies; four-pole (4P) units handle three-phase. On the common modular frames a 2P unit takes two modules and a 4P unit four — but module width isn’t universal, so check the actual datasheet for the device you’re fitting. Hager Malaysia’s CD240J, for instance, is a 2-pole, 2-module device measuring 35mm wide.
Rated current. The 40A or 63A figure is how much load current the device is designed to carry continuously. It is not the leakage at which it trips.
Residual sensitivity. Written in milliamperes — 10mA, 30mA, 100mA, 300mA. This is the imbalance between live and neutral that trips the device. A lower number means it reacts to less leakage, so 10mA is more sensitive than 30mA, and 100mA and 300mA are less sensitive still. Different sensitivities suit different circuits, which is why Malaysian rules specify more than one value (more on that below).
Residual type. This is the letter that trips people up. It describes which shapes of fault current the device is specified to detect, defined in IEC 60755. Type AC detects sinusoidal alternating residual current only. Type A also detects pulsating DC residual current, the kind produced by diode or thyristor rectifier circuits in single-phase electronic loads. Type F adds detection for composite multi-frequency residual current and is aimed at single-phase variable-speed drives. Type B extends to smooth DC residual current as well, for three-phase rectifier loads such as variable-speed drives, PV inverters and EV charging equipment.
Two caveats stop this being a simple ladder. Each type is specified against particular test waveforms, so whether a device is appropriate comes from the equipment it’s protecting and the device’s own specification — a Type A device is not automatically right just because it’s “higher” than Type AC. And the letter here has nothing to do with an MCB’s B, C, D curve, which describes magnetic trip thresholds. Same alphabet, unrelated meaning.
Maxguard’s RCCB range in detail
Maxguard’s ML63-1 and ML100-1 series is a Malaysian-brand option, and the catalogue is helpfully specific about which variant is which — which matters, because Maxguard sells both Type AC and Type A under the same family name. The model code is what distinguishes them, not the series.
Type AC devices carry an N suffix; Type A carries an A. A 40A two-pole 30mA Type AC unit is E40203N, and the equivalent Type A is E40203A. A 63A two-pole 30mA Type A is E63203A. The four-pole codes put a 4 in the pole position: E40403A for 40A 4P 30mA Type A, and E63410A for 63A 4P 100mA Type A.
Sensitivities span 10, 30, 100 and 300mA. The 10mA option appears once, as E25201N — a 25A 2P Type AC device. The 300mA versions are Type AC only in the catalogue, and the 100A ML100-1 family tops out in four-pole Type AC: E100403N (30mA), E100410N (100mA) and E100430N (300mA). If you need Type A, the catalogue’s range is narrower than the family page suggests, so match the exact code.
These are IEC 61008-2-1 devices, rated 230/400V and 240/415V at 50/60Hz, IP20, pollution degree 3, with over 2,000 operating cycles. Maxguard also quotes a conditional surge current proof of 3,000A at 8/20µs.
One number to read carefully: the catalogue lists a “rated conditional short-circuit breaking capacity (Icn) of 10kA, with 10kA back-up fuse”. That conditional rating is stated with the manufacturer’s own specified backup protection upstream — so it is a rating that depends on a suitable fuse being there, not a stand-alone short-circuit rating the way an MCB’s Icn is. Don’t order an RCCB expecting it to clear a fault on its own.
Schneider’s residual ranges and the Hager comparison
Schneider’s Acti9 iID is its modular residual-current range, and the four Type A 30mA models Malaysian retailer Exerlon groups together show how the codes work:
- A9R51240 — 2P, 40A, 30mA, Type A
- A9R51263 — 2P, 63A, 30mA, Type A
- A9R51440 — 4P, 40A, 30mA, Type A
- A9R51463 — 4P, 63A, 30mA, Type A
Those four are the 30mA Type A models one retailer lists side by side — not the whole Acti9 iID family, which spans wider ratings and other residual types; the Acti9 iID page covers all 110 references on Schneider Malaysia’s list. On that retailer’s online item prices, the four run from RM250 for the 2P/40A up to RM420 for the 4P/63A, and the step from two poles to four costs more than the step from 40A to 63A within the same pole count. Those are item prices, not delivered quotes, and they change — use them as a rough reference and confirm the current offer.
Schneider’s Easy9 line is the residential and small-business range. Its RCCBs are Type AC apart from one 10mA Type A model, and the exact variant you get depends on the order code. The Easy9 and Acti9 overviews compare the two series.
Hager’s CD240J is a comparable 2-pole, 40A, 30mA Type A device on Hager Malaysia’s catalogue, 35mm wide with a 6kA rated conditional short-circuit current to EN 61008-1 and a 1.5kA making and breaking capacity. Hager Malaysia lists 63 RCCBs, including four 10mA models; its product page gives ratings, not Malaysian stock or pricing. The Hager RCCB page covers those 10mA models and Malaysian prices, and the Hager brand page the rest of what we’ve researched.
Himel and ABB, and the 10mA price spread
Two more brands that Malaysian electricians name often sit at opposite ends of the price range. Neither has a Malaysian product list online, so our pages build their tables from Malaysian distributor and price-list sources.
Himel, a budget brand priced around Maxguard, sells two RCCB series, HDB6VR and HDB3VR, in 2 and 4 poles from 25A to 100A. The code spells the rating out: HDB6VR225LC is 2-pole, 25A, 10mA (L), Type AC (C). Each series has one 10mA rating, 2P 25A Type AC, and the HDB3VR adds three Type A codes at 30mA: HDB3VR240SA, HDB3VR263SA and HDB3VR440SA. We found no Malaysian datasheet for either series, so their standard part and short-circuit rating aren’t known here.
ABB, in the premium tier, sells the F202 and F204 (and FH202/FH204). ABB’s designation also spells the rating out: F202 AC-25/0.01 is 2-pole, Type AC, 25A, 0.01A (10mA). The 10mA options in KVC’s catalogue are all 2-pole: F202 AC-16/0.01, F202 AC-25/0.01 and the Type A F202 A-16/0.01. JKR’s approved list records ABB’s RCCBs as made in Italy, and Himel’s as made in China.
At the water-heater rating, 2-pole 25A 10mA Type AC, the spread across researched brands is wide. These are October 2026 shop or marketplace prices, not like-for-like datasheet comparisons:
| Brand and code | Price seen |
|---|---|
| Himel HDB6VR225LC | RM50–62.55 |
| Maxguard E25201N | RM91.40 |
| Schneider Easy9 EZ9R14225 | RM100–121.53 |
| ABB F202 AC-25/0.01 | RM149.32–220 |
| Hager CC225B | RM215–253.65 |
Buy by the full code
The habit that saves the most trouble is ordering by full model code. “40 amp RCCB” could be 2-pole or 4-pole, 30mA or 100mA, Type AC or Type A — eight different products. E40203A, A9R51240, CD240J, HDB3VR240SA and F202 A-63/0.03 each name exactly one device.
On the supply side, Maxguard’s codes and sensitivities are published on its ML63-1/ML100-1 product page and in its catalogue, and its devices reach buyers through electrical wholesalers. Schneider’s Acti9 and Easy9 residual devices come through its distributor network, which in Johor Bahru includes Maydenki, Synoview Electric and Genuine Electric. Whether a branch stocks a specific code is a separate question from whether the brand is sold locally, so it’s worth confirming before a trip.
Equipment that changes the type
Type A handles the single-phase electronic loads common in a modern house, but it isn’t automatically the answer for everything.
Single-phase variable-speed drives — increasingly common in washing machines and air-conditioners — can produce residual current waveforms that call for Type F. Three-phase rectifier loads, including larger variable-speed drives, PV inverters and EV charging equipment, can produce smooth DC residual current that only Type B detects. Whether a particular EV charger or inverter needs Type B comes from that equipment and the installation design — not from a general rule that “Type A is for EV chargers”. If a manufacturer specifies Type B for their equipment, a Type A device does not satisfy it.
What Malaysian rules expect
Malaysia’s domestic wiring requirements are set out in the Suruhanjaya Tenaga Garis Panduan Pendawaian Elektrik Pepasangan Domestik. The guide requires residual-current protection on final circuits using a current-operated device (the older voltage-operated ELCB is not permitted), and its sensitivity requirements are more specific than the single 30mA figure many people assume.
Under Rule 36 of the Electricity Regulations 1994, as set out in the guide:
- 10mA or less for public entertainment premises and for floors likely to be wet or low-resistance walls and enclosures — the guide’s examples include pools, garden and fence lighting, and water-heater circuits.
- 30mA or less for equipment, apparatus or tools held in the hand — for example socket outlet circuits.
- 100mA or less for other installations — for example lighting, fan and air-conditioning circuits.
The guide also classifies residual devices by their DC response (types AC, A, B and F), notes Type AC as the most common in Malaysian home wiring, encourages Type A where many electronic devices are used, and encourages Types B and F where inverter-equipped equipment is installed. That guidance lines up with the type discussion above: Type AC covers the traditional case, Type A adds detection for the pulsating DC from single-phase electronics, and Types B and F extend it to the composite and smooth DC waveforms that inverter-driven loads can produce. It requires the RCCB’s rated conditional short-circuit current to be at least the upstream breaker’s breaking capacity.
Selection itself depends on the supply arrangement, the earthing system, how devices discriminate with upstream and downstream protection, and the loads involved — the things an installer has to work out for a specific board. Use the labels above to identify the right product and the right code, then let a competent person confirm the design.
Ranges across brands
ABB F200 and FH200 RCCBs (Malaysia)
ABB's F200 and FH200 residual current circuit breakers as listed in Malaysia: 2-pole F202/FH202 and 4-pole F204/FH204, 16–125A, 10/30/100/300/500mA, Type AC and Type A. The 10mA options in KVC's catalogue are 2-pole only: F202 AC-16/0.01, F202 AC-25/0.01 and the Type A F202 A-16/0.01. Codes from KVC's catalogue (October 2026); F202/F204/FH202/FH204 are ABB's approved RCCB models on JKR's eMAL list, made in Italy.
- Where the codes come from
- ABB's product pages are a global catalogue; ABB Malaysia's own site didn't load during this research. Rows are the plain Type AC and Type A F200/FH200 codes in KVC's Malaysian catalogue
- Reading the designation
- F202 AC-25/0.01 = 2-pole, Type AC, 25A, 0.01A (10mA). F204 = 4-pole; FH = the FH200 line; A instead of AC = Type A. ABB's order code (2CSF…) is shown in the table
- 10mA models
- F202 AC-16/0.01, F202 AC-25/0.01 (Type AC) and F202 A-16/0.01 (Type A). No 10mA above 25A and no 4-pole 10mA in KVC's catalogue
- Order-code note
- F204 A-100/0.03 and A-100/0.3 carry order codes 2CSF204123…, the same prefix as KVC's F204 A-125/0,03-L; they may be a variant of the plain F204 A — confirm with the supplier
- Type A at KVC
- F202 A-25/0.03, A-63/0.03, A-40/0.1, A-25/0.3, A-40/0.3, A-63/0.3; F204 A-40/0.03, A-63/0.03, A-100/0.03, A-125/0.03, A-40/0.1, A-63/0.1, A-40/0.3, A-100/0.3
- Left out of the table
- KVC also lists AP-R (high-immunity), selective (S), Type B, 110V and '-L' versions and auto-reclosing units
- KVC title errors
- Some KVC titles state the wrong rating (e.g. 'F204 A-63/0.03 … 300MA', 'F204 A-63/0.1 … 40A'); the table follows ABB's designation
- JKR eMAL
- Approved RCCB models F202 and F204 (AC-40 and AC-63 at 0.03 and 0.1) and the same in FH202/FH204, supplier ABB Malaysia Sdn Bhd, made in Italy
- Not established
- No Malaysian datasheet was read for the standard part (IEC 61008-2-1 voltage-independent or not) or conditional short-circuit rating
Manufacturer information
- KVC catalogue search – ABB F202
- KVC catalogue search – ABB F204
- JKR eMAL approved list – RCCB
- JKR eMAL approved models – ABB
- BigGo Malaysia – ABB F202 RCCB (marketplace store prices)
- BigGo Malaysia – ABB F204 (marketplace store prices)
- KVC – F202 A-16/0.01 (2CSF202101R0160)
- KVC – F202 A-25/0.03 (2CSF202101R1250)
- KVC – F202 A-25/0.3 (2CSF202101R3250)
- KVC – F202 A-40/0,1 (2CSF202101R2400)
- KVC – F202 A-40/0.3 (2CSF202101R3400)
- KVC – F202 A-63/0.03 (2CSF202101R1630)
- KVC – F202 A-63/0.3 (2CSF202101R3630)
- KVC – F202 AC-16/0.01 (2CSF202001R0160)
- KVC – F202 AC-16/0.01 (2CSF202005R0160)
- KVC – F202 AC-25/0.01 (2CSF202001R0250)
- KVC – F202 AC-25/0.1 (2CSF202005R2250)
- KVC – F202 AC-25/0.03 (2CSF202005R1250)
- KVC – F202 AC-25/0.3 (2CSF202005R3250)
- KVC – F202 AC-40/0.1 (2CSF202001R2400)
- KVC – F202 AC-40/0.1 (2CSF202005R2400)
- KVC – F202 AC-40/0.03 (2CSF202005R1400)
- KVC – F202 AC-40/0.3 (2CSF202005R3400)
- KVC – F202 AC-63/0.1 (2CSF202005R2630)
- KVC – F202 AC-63/0.03 (2CSF202005R1630)
- KVC – F202 AC-63/0.3 (2CSF202005R3630)
- KVC – F202 AC-80/0.1 (2CSF202005R2800)
- KVC – F202 AC-80/0.03 (2CSF202001R1800)
- KVC – F202 AC-80/0.3 (2CSF202005R3800)
- KVC – F202 AC-80/0.5 (2CSF202005R4800)
- KVC – F202 AC-100/0.1 (2CSF202005R2900)
- KVC – F202 AC-100/0.03 (2CSF202005R1900)
- KVC – F202 AC-100/0.3 (2CSF202005R3900)
- KVC – F204 A-40/0.1 (2CSF204101R2400)
- KVC – F204 A-40/0,03 (2CSF204101R1400)
- KVC – F204 A-40/0.3 (2CSF204101R3400)
- KVC – F204 A-63/0.1 (2CSF204101R2630)
- KVC – F204 A-63/0.03 (2CSF204101R1630)
- KVC – F204 A-100/0.03 (2CSF204123R1900)
- KVC – F204 A-100/0.3 (2CSF204123R3900)
- KVC – F204 A-125/0,03 (2CSF204101R1950)
- KVC – F204 AC-25/0.1 (2CSF204005R2250)
- KVC – F204 AC-25/0.03 (2CSF204005R1250)
- KVC – F204 AC-25/0.3 (2CSF204005R3250)
- KVC – F204 AC-40/0.1 (2CSF204005R2400)
- KVC – F204 AC-40/0.03 (2CSF204005R1400)
- KVC – F204 AC-40/0.3 (2CSF204005R3400)
- KVC – F204 AC-63/0.1 (2CSF204005R2630)
- KVC – F204 AC-63/0,03 (2CSF204001R1630)
- KVC – F204 AC-63/0.03 (2CSF204005R1630)
- KVC – F204 AC-63/0.3 (2CSF204001R3630)
- KVC – F204AC-63/0,3 (2CSF204005R3630)
- KVC – F204 AC-80/0.1 (2CSF204005R2800)
- KVC – F204 AC-80/0.03 (2CSF204005R1800)
- KVC – F204 AC-80/0.3 (2CSF204005R3800)
- KVC – F204 AC-80/0.5 (2CSF204005R4800)
- KVC – F204 AC-100/0.1 (2CSF204001R2900)
- KVC – F204 AC-100/0.1 (2CSF204005R2900)
- KVC – F204 AC-100/0.03 (2CSF204001R1900)
- KVC – F204 AC-100/0,03 (2CSF204005R1900)
- KVC – F204 AC-100/0.3 (2CSF204005R3900)
- KVC – F204 AC-100/0.5 (2CSF204005R4900)
- KVC – F204 AC-125/0.1 (2CSF204001R2950)
- KVC – F204 AC-125/0.03 (2CSF204001R1950)
- KVC – F204 AC-125/0.3 (2CSF204001R3950)
- KVC – F204 AC-125/0.5 (2CSF204001R4950)
- KVC – FH202 AC-25/0.1 (2CSF202006R2250)
- KVC – FH202 AC-25/0.03 (2CSF202006R1250)
- KVC – FH202 AC-25/0.3 (2CSF202006R3250)
- KVC – FH202 AC-40/0.1 (2CSF202006R2400)
- KVC – FH202 AC-40/0.03 (2CSF202006R1400)
- KVC – FH202 AC-40/0.3 (2CSF202006R3400)
- KVC – FH202 AC-63/0.1 (2CSF202006R2630)
- KVC – FH202 AC-63/0.03 (2CSF202006R1630)
- KVC – FH202 AC-63/0.3 (2CSF202006R3630)
- KVC – FH204 AC-25/0.1 (1SYF204006R2250)
- KVC – FH204 AC-25/0.1 (2CSF204006R2250)
- KVC – FH204 AC-25/0.3 (1SYF204006R3250)
- KVC – FH204 AC-25/0.3 (2CSF204006R3250)
- KVC – FH204 AC-25/0.03 (2CSF204006R1250)
- KVC – FH204 AC-40/0.1 (2CSF204006R2400)
- KVC – FH204 AC-40/0.03 (2CSF204006R1400)
- KVC – FH204 AC-40/0.3 (2CSF204006R3400)
- KVC – FH204 AC-63/0.1 (2CSF204006R2630)
- KVC – FH204 AC-63/0.03 (2CSF204006R1630)
- KVC – FH204 AC-63/0.3 (2CSF204006R3630)
Hager RCCBs (Malaysia)
Hager residual current circuit breakers on Hager Malaysia's catalogue: 63 references from 16A to 100A at 10, 30, 100, 300 and 500mA, in Type AC, Type A, high-immunity and time-delayed versions. Four are 10mA; the table shows those, the common 2-pole and 4-pole 30mA models and two 100mA models, then the 20 RCCB pages Hager Malaysia keeps outside the category, each marked obsolete, spare part or phase out.
- Malaysian list
- 63 RCCBs in Hager Malaysia's RCCB category: 10mA ×4, 30mA ×25, 100mA ×17, 300mA ×14, 500mA ×3
- 10mA models
- CC216B (2P 16A Type AC), CC225B (2P 25A Type AC), CCA225B (1P+N 25A Type A), CCA540D (1P+N 40A Type A); CCA525D (1P+N 25A Type A) has a Hager Malaysia page marked Obsolete
- Off-list pages
- 20 RCCB pages outside the category: 9 obsolete, 9 spare part, 2 phase out. 10mA: CCA525D only. 30mA: CD216J, CDA580D, CDH225J. 100mA: CEA640D, CEC680B, CNA263N. 300mA: CF225B, CF425B, CFA680D, CFC580B, CFC680B, CP440B, CPC263M, CQ240J, CQ440J. 500mA: CG225B, CG240B, CG425B, CG440B
- Poles
- Hager titles say 2P or 1P+N for the same 2-pole, 2-module design (its spec tables give 2 poles for both); 4P titles are 3P+N, 4 poles
- Residual types
- Type AC (codes ending B, except CCA225B, which is Type A), Type A (J and D), Type A high immunity (CDH, CH, CQ), time-delayed S (CN, CP, CPA; off-list CNA and CPC)
- Conditional short-circuit current (Inc)
- 10kA for Type AC CC/CD/CE/CF/CG…B and the D-suffix Type A series; 6kA for J-suffix Type A, high-immunity and CCA225B; 6kA for the off-list time-delayed CNA263N and CPC263M
- Widths
- 2-pole 35 or 36mm (2 modules); 4-pole 70 or 72mm
- Standards in linked documents
- EN 61008-1 on all datasheets; the EU declaration for CCA540D and the listed CDA/CEA/CFA 5xx/6xx D models also lists EN/IEC 61008-2-1 (voltage-independent); the declaration for the CC/CD/CE…B/J series lists EN 61008-1 only
- Also on Hager Malaysia
- RCCB with auto recloser: CDA240SC and CDA263SC (1P+N 40/63A 30mA Type A, 3 modules)
Manufacturer information
- Hager Malaysia – RCCB category
- Hager Malaysia – FAQ, energy distribution
- Hager Malaysia leaflet – RCCB Type A with 10kA Inc (MY-2021_07)
- Hager EU declaration 26.2118 – standard RCCBs 16/125A (linked from Hager Malaysia pages)
- Hager EU declaration 26.1690 – RCCBs 16/63A (linked from Hager Malaysia pages)
- Edaran – Hager category
- Hager Malaysia – CC216B
- BigGo Malaysia – hager rccb 10mA
- Hager Malaysia – CC225B
- KVC – Hager CC225B
- BigGo Malaysia – hager CC225B
- Hager Malaysia – CCA225B
- Edaran – Hager CCA225B
- BigGo Malaysia – hager CCA225B
- Hager Malaysia – CCA540D
- Hager Malaysia – CCA525D
- Hager Malaysia – CD216B
- Hager Malaysia – CD225B
- Hager Malaysia – CD240B
- Hager Malaysia – CD240J
- BigGo Malaysia – hager CD240J
- Hager Malaysia – CD263B
- Hager Malaysia – CD263J
- Hager Malaysia – CDA525D
- Hager Malaysia – CDA540D
- BigGo Malaysia – hager CDA540D
- Hager Malaysia – CDA563D
- Hager Malaysia – CDH240J
- Hager Malaysia – CH263J
- Hager Malaysia – CE240B
- Hager Malaysia – CE263B
- Hager Malaysia – CD440B
- Hager Malaysia – CD440J
- Hager Malaysia – CD463B
- Hager Malaysia – CD463J
- Hager Malaysia – CD216J
- Hager Malaysia – CDA580D
- Hager Malaysia – CDH225J
- Hager Malaysia – CEA640D
- Hager Malaysia – CEC680B
- Hager Malaysia – CF225B
- Hager Malaysia – CF425B
- Hager Malaysia – CFA680D
- Hager Malaysia – CFC580B
- Hager Malaysia – CFC680B
- Hager Malaysia – CG225B
- Hager Malaysia – CG240B
- Hager Malaysia – CG425B
- Hager Malaysia – CG440B
- Hager Malaysia – CNA263N
- Hager Malaysia – CP440B
- Hager Malaysia – CPC263M
- Hager Malaysia – CQ240J
- Hager Malaysia – CQ440J
Himel HDB6VR and HDB3VR RCCBs (Malaysia)
Himel residual current circuit breakers sold in Malaysia: the HDB6VR series (2P and 4P, 25–100A, 10/30/100/300mA, Type AC) and the HDB3VR series, which adds three Type A 30mA codes. One 10mA rating in each series: 2P 25A Type AC. Codes from Himel/Desea's 2021 Malaysian list price and the KVC catalogue (October 2026); both series are on JKR's eMAL approved RCCB list.
- Where the codes come from
- Himel has no Malaysian product site. Rows are the codes in Himel/Desea's Malaysian list price effective 1 September 2021 (HDB6VR) and KVC's catalogue in October 2026 (HDB6VR and HDB3VR)
- Reading the code
- Our reading, checked against every KVC title and Desea description: HDB6VR or HDB3VR, then poles (2 or 4), amps, sensitivity letter (L 10mA, S 30mA, Y 100mA, T 300mA) and type (C = Type AC, A = Type A). HDB6VR225LC = 2P 25A 10mA Type AC
- 10mA models
- HDB6VR225LC and HDB3VR225LC, both 2P 25A Type AC. No 10mA Type A and no 10mA above 25A in the Malaysian sources
- Type A models
- HDB3VR240SA (2P 40A 30mA), HDB3VR263SA (2P 63A 30mA), HDB3VR440SA (4P 40A 30mA)
- HDB6VR range
- 2P 40/63A and 4P 40/63/100A at 30, 100 and 300mA, plus the 2P 25A 10mA; all Type AC (Desea list: 'AC-Type')
- HDB3VR range
- Type AC: 2P 25A at 10, 30 and 100mA; 2P 40 and 63A and 4P 40, 63 and 100A at 30, 100 and 300mA; 2P 100A at 100mA. Type A: three 30mA codes
- JKR eMAL
- HDB6VR and HDB3VR are approved RCCB models on JKR's eMAL list, supplier Desea Sdn Bhd, made in China
- Not established
- No Malaysian datasheet for these series was found, so the standard part (IEC 61008-2-1 voltage-independent or not), width and short-circuit rating are not stated here
- List price 2021 (Desea)
- HDB6VR225LC RM139; 2P 40A 30mA RM131; 2P 40A 100mA RM81; 4P 63A 30mA RM199; 4P 100A 30mA RM565 — dealer list prices before discount
Manufacturer information
- Himel/Desea Malaysian list price, effective 1 Sept 2021 (PDF hosted by Kuasa Jati)
- KVC catalogue search – Himel
- JKR eMAL approved list – RCCB
- JKR eMAL approved models – Himel
- BigGo Malaysia – Himel RCCB (marketplace store prices)
- BigGo Malaysia – Himel RCCB Type A (marketplace store prices)
- Energy Option (Semenyih) – Himel RCCB/ELCB HDB6VR series
- Samajaya Elec Trading – Himel 40A 2P 30mA RCCB (Type A)
- KVC – HDB3VR225LC
- KVC – HDB3VR225SC
- KVC – HDB3VR225YC
- KVC – HDB3VR240SA
- KVC – HDB3VR240SC
- KVC – HDB3VR240TC
- KVC – HDB3VR240YC
- KVC – HDB3VR263SA
- KVC – HDB3VR263SC
- KVC – HDB3VR263TC
- KVC – HDB3VR263YC
- KVC – HDB3VR440SA
- KVC – HDB3VR440SC
- KVC – HDB3VR440TC
- KVC – HDB3VR440YC
- KVC – HDB3VR463SC
- KVC – HDB3VR463TC
- KVC – HDB3VR463YC
- KVC – HDB3VR2100YC
- KVC – HDB3VR4100SC
- KVC – HDB3VR4100TC
- KVC – HDB3VR4100YC
- KVC – HDB6VR225LC
- KVC – HDB6VR240SC
- KVC – HDB6VR240TC
- KVC – HDB6VR240YC
- KVC – HDB6VR263SC
- KVC – HDB6VR263TC
- KVC – HDB6VR263YC
- KVC – HDB6VR440SC
- KVC – HDB6VR440TC
- KVC – HDB6VR440YC
- KVC – HDB6VR463SC
- KVC – HDB6VR463TC
- KVC – HDB6VR463YC
- KVC – HDB6VR4100SC
- KVC – HDB6VR4100TC
- KVC – HDB6VR4100YC
Maxguard ML63-1 and ML100-1 RCCBs
Residual-current circuit breakers offered in 25A, 40A and 63A ML63-1 variants and a 100A ML100-1 family. The manufacturer lists Type AC and Type A options; the family name alone does not identify the waveform type.
- Families
- ML63-1 (25A/40A/63A) and ML100-1 (100A)
- Manufacturer-listed sensitivity options
- 10, 30, 100 and 300mA
- Manufacturer-listed waveform options
- Type AC (order-code suffix N) and Type A (suffix A); the family name alone does not identify the waveform type
- Order codes 2P Type AC
- E40203N (40A 30mA), E40210N (40A 100mA), E63203N (63A 30mA), E63210N (63A 100mA), E40230N (40A 300mA), E63230N (63A 300mA), E25201N (25A 10mA)
- Order codes 2P Type A
- E40203A (40A 30mA), E40210A (40A 100mA), E63203A (63A 30mA), E63210A (63A 100mA)
- Order codes 4P Type AC
- E40403N/E40410N (40A), E63403N/E63410N (63A), E40430N/E63430N (40A/63A 300mA); no Type A 4P 300mA in catalogue
- Order codes 4P Type A
- E40403A (40A 30mA), E40410A (40A 100mA), E63403A (63A 30mA), E63410A (63A 100mA)
- Order codes ML100-1 4P Type AC
- E100403N (100A 30mA), E100410N (100A 100mA), E100430N (100A 300mA)
- Technical data
- IEC 61008-2-1; 230/400V~, 240/415~; 50/60Hz; conditional surge current proof 3000A 8/20µs; rated conditional short-circuit breaking capacity Icn 10kA with 10kA back-up fuse; Icm 500A or 10In; IP20; pollution degree 3; >2000 operating cycles
- Widths and terminals
- 2P = 2 module/36mm, 4P = 4 module/72mm; ML63-1 terminal 1–25mm², ML100-1 1–35mm²; DIN rail EN 50022
- Catalogue breaking capacity note
- The 10kA figure is a conditional short-circuit rating that assumes a 10kA back-up fuse — it is not a stand-alone breaking capacity like an MCB's Icn
- Standard (catalogue)
- IEC 61008-2-1; conditional surge current proof 3000 A 8/20 µs ('anti nuisance tripping'); conditional short-circuit 10 kA with 10 kA back-up fuse
- Width (catalogue)
- 2P 36 mm (2 modules), 4P 72 mm
Schneider Acti9 iID RCCBs
All 110 Acti9 iID residual current circuit breakers on Schneider Malaysia's product list: 2P and 4P, 16–100 A, 10 mA to 500 mA, Types AC, A, A-SI, B-SI and B-EV (electric vehicle), some selective.
- Function
- RCCB — earth-leakage protection only, no overload protection
- Malaysian list
- 110 references (AC 41, A 27, A-SI 17, B-SI 20, B-EV 5), 2P and 4P, 16–100 A
- 10 mA
- A9R10216 (2P 16 A AC), A9R10225 (2P 25 A AC), A9R20225 (2P 25 A A), A9R30225 (2P 25 A A-SI)
- Type B
- B-SI (A9Z6…) and B-EV for electric-vehicle charging (A9Z51…), 30–500 mA, double terminal
- Standards (pages checked)
- A/AC/A-SI: EN/IEC 61008-1; B-SI and B-EV: IEC/EN 61008-2-1 and IEC/EN 62423
- Conditional short-circuit current (pages checked)
- 10 kA (Inc/IΔc) on the five resolved pages
- Prices
- Exerlon Power online prices for four 30 mA Type A refs; 2021 Schneider Malaysia list prices (before trade discounts) where the reference is in the 2021 index
Manufacturer information
- Schneider Acti 9 iID range (Malaysia)
- Exerlon Power listing (variant prices)
- Schneider product specification
- Schneider Electric Malaysia – A9R10216
- Schneider Electric Malaysia – A9R10225
- Schneider Electric Malaysia – A9R20225
- Schneider Electric Malaysia – A9R30225
- Schneider Electric Malaysia – A9R71225
- Schneider Electric Malaysia – A9R71240
- Schneider Electric Malaysia – A9R71263
- Schneider Electric Malaysia – A9R11280
- Schneider Electric Malaysia – A9R11291
- Schneider Electric Malaysia – A9R71425
- Schneider Electric Malaysia – A9Z11425
- Schneider Electric Malaysia – A9R71440
- Schneider Electric Malaysia – A9R71463
- Schneider Electric Malaysia – A9R11480
- Schneider Electric Malaysia – A9R11491
- Schneider Electric Malaysia – A9R51225
- Schneider Electric Malaysia – A9R51263
- Schneider Electric Malaysia – A9R21291
- Schneider Electric Malaysia – A9R51425
- Schneider Electric Malaysia – A9R51440
- Schneider Electric Malaysia – A9R51463
- Schneider Electric Malaysia – A9R21480
- Schneider Electric Malaysia – A9R21491
- Schneider Electric Malaysia – A9R91225
- Schneider Electric Malaysia – A9R91240
- Schneider Electric Malaysia – A9R91263
- Schneider Electric Malaysia – A9R91425
- Schneider Electric Malaysia – A9R91440
- Schneider Electric Malaysia – A9R91463
- Schneider Electric Malaysia – A9R31491
- Schneider Electric Malaysia – A9Z61225
- Schneider Electric Malaysia – A9Z61240
- Schneider Electric Malaysia – A9Z61263
- Schneider Electric Malaysia – A9Z61425
- Schneider Electric Malaysia – A9Z61440
- Schneider Electric Malaysia – A9Z61463
- Schneider Electric Malaysia – A9Z61480
- Schneider Electric Malaysia – A9Z51216
- Schneider Electric Malaysia – A9Z51225
- Schneider Electric Malaysia – A9Z51240
- Schneider Electric Malaysia – A9Z51440
- Schneider Electric Malaysia – A9Z51463
- Schneider Electric Malaysia – A9R12240
- Schneider Electric Malaysia – A9R12263
- Schneider Electric Malaysia – A9R12280
- Schneider Electric Malaysia – A9R12291
- Schneider Electric Malaysia – A9R12440
- Schneider Electric Malaysia – A9R12463
- Schneider Electric Malaysia – A9R12480
- Schneider Electric Malaysia – A9R12491
- Schneider Electric Malaysia – A9R22240
- Schneider Electric Malaysia – A9R22263
- Schneider Electric Malaysia – A9R22440
- Schneider Electric Malaysia – A9R22463
- Schneider Electric Malaysia – A9R74225
- Schneider Electric Malaysia – A9R74240
- Schneider Electric Malaysia – A9R74263
- Schneider Electric Malaysia – A9R15263
- Schneider Electric Malaysia – A9R14280
- Schneider Electric Malaysia – A9R15280
- Schneider Electric Malaysia – A9R14291
- Schneider Electric Malaysia – A9R15291
- Schneider Electric Malaysia – A9R74425
- Schneider Electric Malaysia – A9R74440
- Schneider Electric Malaysia – A9R15440
- Schneider Electric Malaysia – A9R74463
- Schneider Electric Malaysia – A9R15463
- Schneider Electric Malaysia – A9R14480
- Schneider Electric Malaysia – A9R15480
- Schneider Electric Malaysia – A9R14491
- Schneider Electric Malaysia – A9R15491
- Schneider Electric Malaysia – A9R24225
- Schneider Electric Malaysia – A9R24240
- Schneider Electric Malaysia – A9R25240
- Schneider Electric Malaysia – A9R24291
- Schneider Electric Malaysia – A9R24440
- Schneider Electric Malaysia – A9R25440
- Schneider Electric Malaysia – A9R24463
- Schneider Electric Malaysia – A9R25463
- Schneider Electric Malaysia – A9R24480
- Schneider Electric Malaysia – A9R24491
- Schneider Electric Malaysia – A9R05491
- Schneider Electric Malaysia – A9R25491
- Schneider Electric Malaysia – A9R35240
- Schneider Electric Malaysia – A9R35263
- Schneider Electric Malaysia – A9R35291
- Schneider Electric Malaysia – A9R35440
- Schneider Electric Malaysia – A9R34463
- Schneider Electric Malaysia – A9R35463
- Schneider Electric Malaysia – A9R34491
- Schneider Electric Malaysia – A9R35491
- Schneider Electric Malaysia – A9Z64225
- Schneider Electric Malaysia – A9Z64240
- Schneider Electric Malaysia – A9Z64263
- Schneider Electric Malaysia – A9Z64425
- Schneider Electric Malaysia – A9Z64440
- Schneider Electric Malaysia – A9Z65440
- Schneider Electric Malaysia – A9Z64463
- Schneider Electric Malaysia – A9Z65463
- Schneider Electric Malaysia – A9Z64480
- Schneider Electric Malaysia – A9Z65480
- Schneider Electric Malaysia – A9R16463
- Schneider Electric Malaysia – A9R17463
- Schneider Electric Malaysia – A9R16480
- Schneider Electric Malaysia – A9R26491
- Schneider Electric Malaysia – A9R37463
- Schneider Electric Malaysia – A9Z66440
- Schneider Electric Malaysia – A9Z66463
- Schneider Electric Malaysia – A9Z66480
Schneider Acti9 series
Schneider's Acti9 modular system as researched in Malaysia: iC60 MCBs, iC60 RCBOs, iDPN Vigi RCBOs, Vigi iC60 add-on blocks, iID RCCBs and iPRD surge arresters. Larger Malaysian lists than Easy9, with higher breaking-capacity tiers, more curves, residual types up to Type B and voltage-independent RCBOs.
- Members researched
- iC60 MCB (429 references), iC60 RCBO (9), iDPN Vigi (55), Vigi iC60 (48), iID (110), iPRD (26)
- 10mA options
- iID RCCB 2P 16/25A; iDPN Vigi 1P+N 10/16A Type A; Vigi iC60 block 2P 25A Type AC; none in the iC60 RCBO
- Not researched yet
- iPF K, iPRF1/PRD1 surge arresters and other Acti9 auxiliaries on the Malaysian lists
Manufacturer information
- Schneider Malaysia range page – acti9-ic60
- Schneider Malaysia range page – acti9-ic60-rcbo
- Schneider Malaysia range page – acti9-idpn-vigi
- Schneider Malaysia range page – acti9-vigi-ic60
- Schneider Malaysia range page – acti9-iid
- Schneider Malaysia range page – acti9-iprd
- Schneider Malaysia price list, August 2021 (hosted by a Malaysian seller)
Schneider Easy9 RCCBs
Schneider's Easy9 residual-current circuit breakers (RCCBs) for residential and small commercial boards: 2- and 4-pole, 25–63 A, 10–300 mA, Type AC plus one 10 mA Type A reference on Schneider Malaysia's pages.
- Family
- Easy9
- Function
- RCCB — residual-current protection, no overload protection
- Poles
- 2P (230 V AC) and 4P (400 V AC)
- Rated current
- 25, 40, 63 A
- Sensitivity
- 10, 30, 100, 300 mA
- Residual type
- Type AC; Schneider Malaysia's pages list one Type A reference, 2P 25 A 10 mA (EZ9R26225)
- Conditional short-circuit current (Inc)
- 6 kA in Schneider's descriptions for most references; 4.5 kA for EZ9R14225; not stated for EZ9R56425
Manufacturer information
- Schneider Easy9 RCCB range (Malaysia)
- Schneider Electric Malaysia – EZ9R14225
- YK Electrical Supplies – Schneider RCCB list
- Schneider Electric Malaysia – EZ9R26225
- Chin Chun Hardware – Easy9 RCCB
- Schneider Electric Malaysia – EZ9R36225
- Plus Power Solution – Easy9 RCCB 2P AC type
- Schneider Electric Malaysia – EZ9R36240
- Schneider Electric Malaysia – EZ9R36263
- Schneider Electric Malaysia – EZ9R36425
- Schneider Electric Malaysia – EZ9R36440
- Plus Power Solution – Easy9 RCCB 4P AC type
- Schneider Electric Malaysia – EZ9R36463
- Chin Chun Hardware – Easy9 RCCB
- Schneider Electric Malaysia – EZ9R56225
- Schneider Electric Malaysia – EZ9R56240
- Schneider Electric Malaysia – EZ9R56263
- Schneider Electric Malaysia – EZ9R56425
- Schneider Electric Malaysia – EZ9R56440
- Schneider Electric Malaysia – EZ9R56463
- Schneider Electric Malaysia – EZ9R66225
- Schneider Electric Malaysia – EZ9R66240
- Schneider Electric Malaysia – EZ9R66263
- Schneider Electric Malaysia – EZ9R66425
- Schneider Electric Malaysia – EZ9R66440
- Schneider Electric Malaysia – EZ9R66463
Schneider Easy9 series
Schneider's Easy9 modular series for home and small-business boards as researched in Malaysia: MCBs, RCCBs and RCBOs. As of October 2026 the Malaysian lists have 75 MCBs, 20 RCCBs and 2 RCBOs, and the Easy9 SPD range has no products on the Malaysian list.
- Members researched
- Easy9 MCB, Easy9 RCCB, Easy9 RCBO
- Not on the Malaysian list
- Easy9 SPD: Schneider Malaysia has a range page but its product list is empty (a Shopee store lists EZ9L33620)
- 10mA options
- RCCB 2P 25A (EZ9R14225 Type AC, EZ9R26225 Type A); RCBO 25A and 32A 1P+N Type A
- 2021 list price vs Acti9 (same rating)
- 2P C25 MCB RM82.20 vs iC60N RM121.00; 2P 25A 10mA AC RCCB RM316.20 vs iID RM540.30 (before trade discounts)
- MCB lines
- 4.5kA (28 refs), 6kA (27) and 10kA (20), all C curve
Models
Hager CDA240D
Hager CDA240D is a two-pole, 40A, 30mA Type A RCCB (6kA conditional short-circuit current, EN 61008-1) documented on a Hager European datasheet. Hager Malaysia has no product page for it, not even one marked obsolete or spare part, and no Malaysian seller listing was found in search; distributors may still hold older stock. Hager Malaysia's comparable current model is CD240J.
- Function
- RCCB without integral overcurrent protection
- Poles
- 2P (1P+N)
- Rated current
- 40A
- Residual sensitivity
- 30mA
- Residual type
- Type A
- Conditional short-circuit current
- 6kA to EN 61008-1
- Making and breaking capacity (Idm)
- 1.5kA
- Width
- 35mm (2 modules)
- Impulse withstand (Uimp)
- 4000V
- Degree of protection
- IP20
- Malaysian status
- No Hager Malaysia product page: Hager Malaysia's product index, which also covers obsolete, spare-part and phase-out pages, has no CDA240D. No Malaysian listing found in search results. Kept for reference: older stock may still be sold. Current comparable model: CD240J (2P 40A 30mA Type A).
- Standards
- Hager's EU declaration 26.1690, which covers CDA240D, lists EN 61008-1 only (not the voltage-independent 61008-2-1).
Sources
Maxguard E25201N
Maxguard E25201N is a 2-pole, 25A 10mA Type AC residual current circuit breaker without integral overcurrent protection.
- Function
- RCCB
- Poles
- 2P
- Rated current
- 25A
- Residual sensitivity
- 10mA
- Residual type
- Type AC
Maxguard E40203A
Maxguard E40203A is a 2-pole, 40A 30mA Type A residual current circuit breaker without integral overcurrent protection.
- Function
- RCCB
- Poles
- 2P
- Rated current
- 40A
- Residual sensitivity
- 30mA
- Residual type
- Type A
Maxguard E40403A
Maxguard E40403A is a 4-pole, 40A 30mA Type A residual current circuit breaker without integral overcurrent protection.
- Function
- RCCB
- Poles
- 4P
- Rated current
- 40A
- Residual sensitivity
- 30mA
- Residual type
- Type A
Maxguard E63203A
Maxguard E63203A is a 2-pole, 63A 30mA Type A residual current circuit breaker without integral overcurrent protection.
- Function
- RCCB
- Poles
- 2P
- Rated current
- 63A
- Residual sensitivity
- 30mA
- Residual type
- Type A
Schneider A9R51240 — Acti9 iID
Two-pole, 40A, 30mA Type A residual current circuit breaker in Schneider’s Acti9 iID range.
- Function
- RCCB without integral overcurrent protection
- Poles
- 2P; neutral on the left
- Rated current
- 40A
- Residual sensitivity
- 30mA
- Residual type and timing
- Type A; instantaneous
- Voltage
- 230–240V AC, 50/60Hz
- Width and mounting
- 36mm; 35mm DIN rail
Schneider A9R51263
2P, 63A, 30mA, Type A
Schneider A9R51440
4P, 40A, 30mA, Type A
Schneider A9R51463
4P, 63A, 30mA, Type A
Suppliers in this directory
Suppliers and locations
1 suppliers
- IMS Motionet Sdn Bhd
Industrial automation company and Schneider Electric authorised distributor based in Simpang Ampat, Penang. Distributes electrical control and motion components from Schneider, Delta, Kollmorgen, Sanyo Denki and others, and builds its own automation systems including smart screwing, intelligent maglev transfer, robotics/AMR and machine vision.